Star and Delta connection — Engineering Notes Online
STAR OR WYE(Y)-CONNCETED SYSTEM
This is the method of connecting the separate phases of three-phase system. This system is obtained by joining together similar ends, either the start or the finish , the others ends are joined to the line wire.The common point N is called neutral or star point at which the similar ends are connected.The voltage between any line and the neutral point i.e voltage across the phase winding is called the phase voltage and the voltage between any two outer is called the line voltage.The neutral point is connected to the earth.
The arrow heads on emfs and currents indicate the positive direction.A positive directions of emfs are taken from star point outwards.The three phases is numbered as 1,2,3 or a,b,c or R,Y,B.usually it is numbered as R,Y,B i.e the three natural colors red,yellow and blue.There are mainly two phase sequences namely RYB and RBY. RYB is taken as positive and RBY as negative.
The emf induced in 3 phases are shown above.In star connection there are two windings between each pair of outer and due to joining of similar ends together the emf induced in them are in opposition.The potential difference between the two outer known as line voltage,is the phasor difference of phases emfs of the two phases.
The potential difference between outer R and Y or the line voltage E RY is the phasor difference of phase emfs ER and
since phase angle between phasors
From phasor diagram
similarly potential difference between outers Y and B or the line voltage
and potential difference between outers B and R or the line voltage
since in star-connected system each line conductor is connected to separate phase,current flowing through the lines and phases are same.
phase voltages and currents in a balanced three-phase circuit is written as:
where ψ is the phase angle between phase voltage and phase current.
Total instantaneous power,
The sum of the three second harmonic oscillating terms which have a progressive phase differences of 120 degree is Zero.The instantaneous power in a 3-phase balanced system is constant and equal to three times the average power per phase.
Total power (p)=√3 *line voltage*power factor
Total apparent power
In balanced star-connected system
- Line voltage are 120° apart.
- Line voltages are 30° ahead of the respective phase voltages.
- Line voltages are √3 times of phase voltages.
- Line currents are equal to phase currents.
- The angle between line currents and the corresponding line voltages is(30° ±ψ);+ve for lagging currents and -ve for leading currents.
where cosψ is the angle between respective phase current and phase voltage(not between line current and line voltage).
MESH OR DELTA(Δ) connected system
pic source:circuit Globe
From the above figure,when the starting end of one coil is connected to the finishing end of another coil ,delta connection is obtained.The directions of emfs in the coil have been taken as positive from start end to finish end.The current phasors are shown in above figure:
Line currents
since phase angle between phase current phasors I YR and -I BR is 60°,
Assuming balanced load
The phase current in each winding is equal and let it be equal to Ip.
Line current
Similarly line current
since in delta-connected system ,only one phase is included between any pair of line outers,potential difference between the line outers,called line voltage and is equal to phase voltage.
i.e. Line voltage EL=phase voltage Ep
i.e Total power output=√3 *line current*power factor
Apparent power
Total reactive power,Q
In balanced delta-connected system:
- Line currents are 120° apart.
- Line currents are 30° behind the respective phase currents.
- Line currents are √3 times of phase currents.
- Line voltages are equal to phase voltages.
- The angle between line currents and the corresponding line voltages is(30° ±ψ);+ve for lagging currents and -ve for leading currents.same as in star system.
- where cosψ is the angle between respective phase current and phase voltage(not between line current and line voltage).
- In balanced system,the resultant emf in the closed circuit will be Zero.
There will be no circulating current in the mesh if no load is connected to the lines.
Conversion of balanced load system from STAR TO DELTA AND VICE VERSA
Any balanced load system can be replaced by an equivalent delta-connected system or vice-versa because of relationship between phase and line voltages and currents.
For example, a balanced star-connected load having an impedance of magnitude Z with a power factor cosψ in each phase can be replaced by an equivalent delta-connected load having an impedance of magnitude 3Z and power factor cosψ in each phase.
For a balanced star-connecetd load,
For the same line in delta-connected system values of voltage and current as in case of star-connected system
comparing (i) and (ii) we get,
Originally published at https://engineeringnotesonline.com on April 2, 2020.